Elcon International – SA10A Switch Analyser

Request Quote

Brochure - Elcon - SA10

Description

For professional circuit-breaker analysis

The SA10 is the circuit breaker timer developed by professionals for professionals. It has a built-in micro Ohm meter/Ductor for measuring of static and dynamic resistance of the breaker poles. It only weighs 11,6 kg/26 lbs.The versatility and precision that this unity offers is, without question unchallenged,and it will indeed be your best partner when testing circuit breakers.Tests in areas with high induction at known problematic substations has proven the SA10 to be the only circuit breaker timer that could withstand these extreme conditions. It’s rugged, it’s small and highly appreciated by our customers.

SA10 features

  • Robust and easy to use HV breaker analyser
  • Results recorded directly to notebook PC with BTS11 software for analysis
  • Rugged and lightweight
  • Can test point-on-wave breaker & first trip analysis
  • Built in 200A DC micro-ohmmeter  measuring function
  • Measures static & dynamic resistance for checking condition of arcing contacts
  • Full motion analysis with either digital or analogue motion transducer
  • The well-known powerful analysing software BTS11 included
  • Built in a small metal carrying case
  • Fully compatible with our factory line test equipment
  • No panel switches, just two push buttons: Open and Close
  • Supports both digital and analogue transducers
  • The only field test equipment with a built-in micro ohm measuring function. 200A!
  • Possibility to use the “first trip” analysing method
  • Weighs only 11,6 kg/26 lb
  • Automatic measurement of coil and motor current/voltage
  • Designed for both offline and online analysis of circuit breakers

Contact timing

The contact input modules of SA10 supplies 120 VDC at open contacts and 100 mA at closed. The evaluation logic also distinguishes between a possible preinsertion and the main contact in the same operation. It is also possible to measure the value of the preinsertion resistor with a reference shunt. Timing for both the preinsertion and the main contact is guaranteed in any switchyard and at any system voltage.

Number of main contact timing channels: 12(x2)
Number of auxiliary contact channels: 6
(The aux inputs can in environments with low induction also be used as main contact inputs).

Coils and motor

Automatic measuring of circuit breaker coil and motor current/voltage. Together with an adjustable power unit it is very easy to perform minimum function voltage test on the coils.
The SA10 uses 1 analogue channel to measure coil voltage and current and 1 channel to measure motor voltage and current. For the coil, 35 A AC/DC is possible for continuous measurement, and for the motor, 50A AC/DC. However, if necessary, higher currents will pass for shorter periods.

Motion measurements

The SA10 supports both analogue and digital transducers. A wide range of transducer fastenings can also be supplied. Elcon International is the official world wide supplier of transducer fastenings for ABB Breakers.

Number of digital transducer inputs: 3
Number of analogue transducer inputs: 3

Analog inputs

All in all, the SA10 has 11 analog inputs. However, since our intention is to provide you with a test equipment that is user-friendly and circuit breaker-oriented, they have been preset to handle specific relevant functions such as coil and motor voltages, currents, analog motion transducers etc.

It is of course possible to set most of the inputs to handle other types of related input signals, such as pressure sensors or temperature sensors or any other type of analogue signal that may be relevant.

Static and dynamic resistance

As the only field test equipment on the market with a built-in micro ohm meter, it is a complete and versatile unit. It generates 200 ADC and the value is automatically recorded into the system together with your other measurements. In order to view the breaker pole’s exact behavior during an operation, the dynamic resistance measurement function offers great diagnostic possibilities.

Switch sync breakers

Upon switching for example capacitor banks and shunt reactors it is common to use a switch-sync relay for the cb. The SA10 allows for full analysis of the point-on-wave switching technology.

Both side grounded

To ensure the highest possible level of personal safety during testing is it recommended to have the circuit breaker grounded on both sides.

With the accessory DCM it is very easy to fulfill the safety standards.

Communication

Standards RS232 communication is default. However, in order to comply with safety regulations a bluetooth communication kit is available, which allows the user to take his laptop pc and move up to 100 m (328 ft) away from the test-object.

First-trip or on-line analysis

In order to fully evaluate the condition of the circuit breaker mechanism, the SA10 provides inputs to test the breaker during an on-line operation. By doing that you can capture the “First Trip” of a breaker that has been stationary for a long time, and by that display how the breaker would perform in an actual fault situation. Both trip and close operations are possible on-line.